PLC和人機界面干擾解決方法
發布時間:2022-11-15 閱讀次數:842次

PLC、人(ren)機界面現場應(ying)用(yong)時的抗干擾(rao)問題,是復(fu)雜而細致的。抗干擾(rao)性(xing)設計是一個十分復(fu)雜的系統性(xing)工(gong)程(cheng),涉及到具(ju)體的輸入輸出設備和(he)工(gong)業現場的具(ju)體環境。

 

要求我們要綜合考慮(lv)各方面(mian)的(de)因素(su),必須根據現(xian)場的(de)實際情況,從減少干擾(rao)源、切斷(duan)干擾(rao)途徑等(deng)方面(mian)進(jin)行全面(mian)的(de)考慮(lv),充分利用各種抗(kang)干擾(rao)措(cuo)施來(lai)進(jin)行可編程(cheng)控(kong)制器、人(ren)機界(jie)面(mian)的(de)設計(ji)。才能真正提高(gao)可編程(cheng)控(kong)制器、人(ren)機界(jie)面(mian)HMI現(xian)場應用時的(de)抗(kang)干擾(rao)能力(li),確保系統安全穩(wen)定(ding)運行。

 

1、PLC控制器抗干擾的軟件措施

由于電(dian)磁干擾(rao)(rao)(rao)的(de)復雜性(xing),僅(jin)采取硬件抗(kang)干擾(rao)(rao)(rao)措施(shi)是不夠的(de),要用PLC控制(zhi)器的(de)軟(ruan)件抗(kang)干擾(rao)(rao)(rao)技(ji)術來(lai)加以配合,進一步(bu)提高(gao)系統的(de)可靠性(xing)。采用數字濾波和(he)工頻整形采樣、定時校(xiao)正參考(kao)點電(dian)位(wei)等措施(shi),有效消除周(zhou)期性(xing)干擾(rao)(rao)(rao)、防止電(dian)位(wei)漂移。采用信息冗余技(ji)術,設計相應的(de)軟(ruan)件標志位(wei);采用間(jian)接跳轉,設置軟(ruan)件保護等。

例如對(dui)開關量輸入(ru)信號(hao),采(cai)用定時器延(yan)時的方式多次讀(du)入(ru),結果(guo)一致再確認(ren)有(you)效(xiao),提高了軟件(jian)的可(ke)靠性。

 

2、正確選擇接地點,完善接地系統。

良好的接地是(shi)(shi)保證PLC控制器(qi)可(ke)(ke)靠工作的重要條件,可(ke)(ke)以避免偶然發生的電壓沖擊危害,還(huan)可(ke)(ke)以抑制干擾。完善的接地系(xi)統是(shi)(shi)PLC控制器(qi)抗(kang)電磁干擾的重要措施之一。

PLC控(kong)制器屬高速低電(dian)平控(kong)制裝置,應(ying)(ying)采用直(zhi)接(jie)接(jie)地(di)(di)方式。為(wei)了抑(yi)制加在電(dian)源及輸入端、輸出端的干擾,應(ying)(ying)給PLC控(kong)制器接(jie)上專用地(di)(di)線,接(jie)地(di)(di)點(dian)應(ying)(ying)與(yu)動力設備的接(jie)地(di)(di)點(dian)分開。若達不到這種要(yao)求,也必須做到與(yu)其他設備公共(gong)接(jie)地(di)(di),禁止與(yu)其他設備串(chuan)聯接(jie)地(di)(di)。接(jie)地(di)(di)點(dian)應(ying)(ying)盡(jin)可能靠近PLC控(kong)制器。

集中布置(zhi)的PLC控制(zhi)器適于(yu)并聯一點接(jie)(jie)(jie)(jie)(jie)地(di)方式(shi),各裝置(zhi)的柜體(ti)中心接(jie)(jie)(jie)(jie)(jie)地(di)點以單(dan)獨的接(jie)(jie)(jie)(jie)(jie)地(di)線(xian)引向(xiang)接(jie)(jie)(jie)(jie)(jie)地(di)極(ji)。分散布置(zhi)的PLC控制(zhi)器,應采用串聯一點接(jie)(jie)(jie)(jie)(jie)地(di)方式(shi)。接(jie)(jie)(jie)(jie)(jie)地(di)極(ji)的接(jie)(jie)(jie)(jie)(jie)地(di)電阻(zu)小(xiao)于(yu)2Ω,接(jie)(jie)(jie)(jie)(jie)地(di)極(ji)最好埋在(zai)距建(jian)筑物10~15m遠處,而且(qie)PLC控制(zhi)器接(jie)(jie)(jie)(jie)(jie)地(di)點必(bi)須與強電設備接(jie)(jie)(jie)(jie)(jie)地(di)點相距10m以上。如(ru)果要(yao)用擴展單(dan)元(yuan),其接(jie)(jie)(jie)(jie)(jie)地(di)點應與基本單(dan)元(yuan)的接(jie)(jie)(jie)(jie)(jie)地(di)點接(jie)(jie)(jie)(jie)(jie)在(zai)一起。

信號源接(jie)(jie)(jie)地(di)時(shi),屏蔽(bi)層應(ying)在信號側(ce)接(jie)(jie)(jie)地(di);信號源不接(jie)(jie)(jie)地(di)時(shi),應(ying)在PLC控制(zhi)器側(ce)接(jie)(jie)(jie)地(di)。信號線中間(jian)有接(jie)(jie)(jie)頭時(shi),屏蔽(bi)層應(ying)牢固連接(jie)(jie)(jie)并進行(xing)絕緣處(chu)理,各(ge)屏蔽(bi)層應(ying)相互連接(jie)(jie)(jie)好。選擇適當的接(jie)(jie)(jie)地(di)處(chu)單點接(jie)(jie)(jie)地(di),要避免多點接(jie)(jie)(jie)地(di)。

 

3、采用性能優良的電源,抑制電網引入的干擾。

對于PLC控制器(qi)(qi)供(gong)(gong)電的(de)電源(yuan),應采用非動力(li)線(xian)路供(gong)(gong)電,直接從低壓(ya)配電室的(de)主(zhu)母線(xian)上采用專用線(xian)供(gong)(gong)電。選(xuan)用隔(ge)離變(bian)(bian)壓(ya)器(qi)(qi),且變(bian)(bian)壓(ya)器(qi)(qi)容量應比實(shi)際需要大1.2~1.5倍左(zuo)右,還可在隔(ge)離變(bian)(bian)壓(ya)器(qi)(qi)前加(jia)入(ru)濾波器(qi)(qi)。對于變(bian)(bian)送器(qi)(qi)和共(gong)用信號儀(yi)表(biao)供(gong)(gong)電應選(xuan)擇分(fen)布電容小、采用多次隔(ge)離和屏蔽及(ji)漏感技術的(de)配電器(qi)(qi)。

 控制(zhi)器(qi)和I/O系統分別由各自的隔離變壓(ya)器(qi)供(gong)(gong)電(dian),并(bing)與主電(dian)路(lu)(lu)電(dian)源分開(kai)。PLC控制(zhi)器(qi)的24V直(zhi)流電(dian)源盡量不(bu)要給外(wai)圍(wei)的各類傳感器(qi)供(gong)(gong)電(dian),以減少外(wai)圍(wei)傳感器(qi)內(nei)部或供(gong)(gong)電(dian)線路(lu)(lu)短(duan)路(lu)(lu)故障對(dui)PLC控制(zhi)器(qi)的干擾。

此外,為保證(zheng)電(dian)(dian)(dian)(dian)(dian)網(wang)饋電(dian)(dian)(dian)(dian)(dian)不中斷,可(ke)采(cai)用在線式不間斷供(gong)電(dian)(dian)(dian)(dian)(dian)電(dian)(dian)(dian)(dian)(dian)源(UPS)供(gong)電(dian)(dian)(dian)(dian)(dian),UPS具備過壓、欠壓保護(hu)功能、軟件監控(kong)、與電(dian)(dian)(dian)(dian)(dian)網(wang)隔離等功能,可(ke)提高(gao)供(gong)電(dian)(dian)(dian)(dian)(dian)的安全(quan)可(ke)靠性。對于一(yi)些重要的設備,交流供(gong)電(dian)(dian)(dian)(dian)(dian)電(dian)(dian)(dian)(dian)(dian)路可(ke)采(cai)用雙路供(gong)電(dian)(dian)(dian)(dian)(dian)系統。

 

4、正確選擇電纜的和實施敷設,消除可編程控制器、人機界面的空間輻射干擾。

不同類(lei)型(xing)的信(xin)號(hao)分別由不同電(dian)(dian)(dian)纜(lan)傳輸(shu)(shu),采用遠離技術,信(xin)號(hao)電(dian)(dian)(dian)纜(lan)按傳輸(shu)(shu)信(xin)號(hao)種(zhong)類(lei)分層敷設,相(xiang)同類(lei)型(xing)的信(xin)號(hao)線(xian)采用雙絞方式。嚴禁(jin)用同一電(dian)(dian)(dian)纜(lan)的不同導線(xian)同時傳送動力(li)電(dian)(dian)(dian)源(yuan)和(he)信(xin)號(hao),避免信(xin)號(hao)線(xian)與動力(li)電(dian)(dian)(dian)纜(lan)靠近平行敷設,增(zeng)大電(dian)(dian)(dian)纜(lan)之間的夾(jia)角,以減少電(dian)(dian)(dian)磁干擾。

為了減少動(dong)力電(dian)(dian)纜尤(you)其是變頻裝(zhuang)置饋電(dian)(dian)電(dian)(dian)纜的輻(fu)射電(dian)(dian)磁干(gan)擾(rao)(rao),從干(gan)擾(rao)(rao)途徑上阻隔干(gan)擾(rao)(rao)的侵入,要采用屏蔽電(dian)(dian)力電(dian)(dian)纜。

 

5、PLC控制器輸入輸出通道的抗干擾措施

輸(shu)(shu)入(ru)模(mo)塊的(de)(de)濾(lv)波可以降低輸(shu)(shu)入(ru)信(xin)(xin)號(hao)(hao)的(de)(de)線(xian)間的(de)(de)差模(mo)干擾。為了降低輸(shu)(shu)入(ru)信(xin)(xin)號(hao)(hao)與大地(di)間的(de)(de)共模(mo)干擾,PLC控制器要良(liang)好(hao)接地(di)。輸(shu)(shu)入(ru)端有(you)感性(xing)負(fu)載(zai)時,對于交流輸(shu)(shu)入(ru)信(xin)(xin)號(hao)(hao),可在負(fu)載(zai)兩端并接電(dian)(dian)容和(he)電(dian)(dian)阻,對于直流輸(shu)(shu)入(ru)信(xin)(xin)號(hao)(hao)可并接續流二(er)極管。為了抑制輸(shu)(shu)入(ru)信(xin)(xin)號(hao)(hao)線(xian)間的(de)(de)寄生電(dian)(dian)容、與其他線(xian)間的(de)(de)寄生電(dian)(dian)容或耦(ou)合所(suo)產生的(de)(de)感應電(dian)(dian)動勢,可采用RC浪涌吸(xi)收器。

 輸(shu)出(chu)(chu)(chu)為交流(liu)感性負載(zai),可(ke)在負載(zai)兩端并聯RC浪(lang)涌吸(xi)(xi)收器(qi);若為直流(liu)負載(zai),可(ke)并聯續流(liu)二極管(guan),也要盡可(ke)能(neng)靠近負載(zai)。對于開關(guan)量(liang)輸(shu)出(chu)(chu)(chu)的場(chang)合,可(ke)以采用浪(lang)涌吸(xi)(xi)收器(qi)或(huo)晶閘(zha)管(guan)輸(shu)出(chu)(chu)(chu)模塊(kuai)。另外(wai),采用輸(shu)出(chu)(chu)(chu)點(dian)串接中間繼電器(qi)或(huo)光(guang)電耦合措施,可(ke)防止PLC控制器(qi)輸(shu)出(chu)(chu)(chu)點(dian)直接接入電氣控制回路,在電氣上(shang)完全隔離。

 

6、設備選型

在選(xuan)擇(ze)設(she)備時,首先要了解國產PLC生產廠家給出的(de)抗干擾(rao)指標,如(ru)共模(mo)抑制比(bi)、差模(mo)抑制比(bi)、耐壓(ya)能力、允許在多大電場強度(du)和多高頻率的(de)磁場強度(du)環境中工作等,要選(xuan)擇(ze)有較(jiao)高抗干擾(rao)能力的(de)產品(pin),如(ru)采用(yong)浮地技術、隔離性能好的(de)可編程控制器、人機界(jie)面HMI。